Temp. & Humidity Range | -40°C to 100°C / 25 to 98% RH at 25°C |
---|---|
Temp. & Humidity Uniformity |
± 1.5°C / ± 3.0%Ph (No Load) |
Temp. & Humidity Fluctuation |
± 0.5°C / ± 2.5%Ph |
Ramp Up/Down Rate | Heat up rate : 3.0°C/min Pull down rate : 2.0°C/min |
Temperature extremes achievement Time |
Heat up time : from 20 to +100°C (40 Min) Pull down time : from 20 to -40°C (50 Min) |
Chamber Outside Dimensions |
W1500 x D1800 x H2300 (mm) |
Chamber Inside Dimensions |
W1000 x D800 x H1000 (mm) |
Air Circulator | Sirocco Fan |
System | Mechanical Type Double-Stage Compression Cooling |
Capacity | 800L |
Allowable heat load | 2850W |
Provides reliable test results | - Uniform temperature distribution inside the chamber enables testing of multiple test specimens - Minimizes testing errors, enhancing component/product reliability |
---|---|
Wide-range temperature control | - Low-temperature control technology provides a broader temperature control range than any other product - Wide temperature range enables testing under various conditions or extreme environmental conditions |
Provides an environment optimized for various specification tests | - Maintains a constant state even under full load, enabling long-term temperature storage and operation tests - Short heating/cooling times enable rapid temperature cycle tests |